Catalog # Description Die Set
8
The Service Provider
Solutions Guide
800-825-5517 (7 a.m. – 5 p.m. CT) www.graybar.com
Solutions
Supplier Prefix: BUN
Grounding Products
TOWER PROTECTION AND WAVEGUIDE BONDING AND GROUNDING
• Locate air terminal 18 in. above tower and all
antennas.
• Ground antenna support using Burndy
GAR3903TC ground clamp and YA3C-2TC38 lug
for #2 solid copper with TMH289 DURIUM silicon
bronze hardware.
• Locate ground bar near top of tower, below
bends in waveguide cable, and just below cable
entrance to building or near outdoor PCS
switching equipment. The maximum straight
distance allowable between groundbars is 100 ft.
• Connect waveguide grounding kits to ground
bars using Burndy (2) hole compression long
barrel lugs — YA6C-2TC38 and TMH267 DURIUM
mounting hardware, YG14B-2TC2C2C for #2 solid
to grounded buss.
• Connections to the ring ground
shall be UL 467 listed. For direct
burial, use Burndy
HYGROUND
™
products
YGHP58C2W-2TN.
• Bond ice bridge supports
to tower and equipment
ring ground with Burndy
YA3C-2TC38 lugs and
YGHP58C2W-2TN
grounding connectors for
#2 solid.
• Each tower leg shall be
grounded to the tower
ring ground using YA3C-2TC38 lugs and UL-467-listed compression connectors —
Burndy YGHP58C2W-2TN.
• Apply Burndy PENETROX
®
E oxide-inhibiting compound to all contact surfaces.
Remove excess.
(A)YA6C-2TC14 AWG #6 long barrel lug
1
⁄
4”
5
⁄
8”BlueY1MR-TC
YA6C-2TC14E2 AWG #6 long barrel lug
1
⁄
4”
3
⁄
4”BlueY1MR-TC
YA6C-2TC14E1 AWG #6 long barrel lug
1
⁄
4”1” BlueY1MR-TC
YA6C-2TC38 AWG #6 long barrel lug
3
⁄
8”1” BlueY1MR-TC
YA3C-2TC38 #2 solid long barrel lug
3
⁄
8”1” White Y1MR-TC
YA2C-2TC38 #2 stranded long barrel lug
3
⁄
8”1” BrownY1MR-TC
Catalog # Description Bolt Size Hole Space Die Color Crimp Tool
(B) Y1MRTC Full-cycle ratchet hand tool #8, #6, #4, #2 solid, #2 stranded, #2
flex stranded lugs and #6 to #6 C-taps
Catalog # Description Crimp Size
(C) YGHP58C2W-2TN
5
⁄
8”–
1
⁄
2” ground rod to #2 solid – #6 solid U997
copper, (1) continuous run and (1) tap or
up to (2) taps may be connected
(D)YGHC2C2
5
⁄
8”–
1
⁄
2” ground rod to: Run – #6 solid and #2 U-C
stranded, Tap – #6 solid and #2 stranded
(E) YG14B2TC2C2C
5
⁄
8”–
1
⁄
2” ground rod to
1
⁄
4” buss bar to (1) or (2) U1105
#2 solid / #2 stranded taps, suitable for use
with either (1) or (2) conductors, for
continuous uncut conductor applications
(F) GAR3903TC 1
1
⁄
4” to 2” diameter pipe ground clamp to (2)
3
⁄
8” on 1” center lug
Catalog # Description
(G)PEN E-8 PENETROX
®
E oxide-inhibiting compound 8-oz. squeeze bottle
Catalog # Description Size
(H)PAT750C18V Multi-purpose crimping tool for use on tension sleeves, H-taps, C-taps,